| Code | FGCEDP3602RTIEC |
| Nominal Power | 3.600 VA |
| Active power | 3.240 W |
| Power factor | 0,9 |
| Technology | On-Line Double Conversion transformerless (VFI-SS-111) |
| Cooling | Fan cooling |
| Audible noise | < 45 dBA at 1 m |
| Positioning | Tower positioning or Into 19’’ rack (2U) |
| Dimension (UPS) WxHxD | 43,8×8,8×63 cm |
| Dimension (with packing) WxHxD | 76x20x60 cm |
| Wight | 29 Kg |
| Input | |
| Number of phases | 1Ph+N |
| Nominal voltage | 208Vac/220Vac/230Vac/240Vac |
| Input voltage range | 110-300Vac |
| Nominal frequency | 50/60 Hz (selectable) |
| Input frequency range (On-Line mode) | +/- 7% |
| Input power factor | 0,99 |
| Output | |
| Number of phases | 1Ph+N |
| Nominal voltage | 208Vac/220Vac/230Vac/240Vac (selectable) |
| Static voltage Regulation at %100 linear load (On-Line and battery mode) | ±1% |
| Voltage THD at rated linear load | <2% (linear load), <8% (non-linear load) |
| Crest factor | 3:1 |
| Frequency | 50/60 Hz (selectable) |
| Free running frequency | ±0,2 Hz |
| Inverter waveform | Sinewave |
| Overload capability | 110% only audible warning, 110-130% for 30 sec, >130% for 100 ms |
| Efficiency | 94%, calculated in double conversion modeto 100% load according to standard 62040-3 |
| Transfer time | 0 ms (On-Line) |
| Battery | |
| Type | Lead acid, sealed, maintenance free |
| Backup time (Typical) | 10-30 min |
| Extended autonomy | External Battery Box (optional) |
| Environmental specification | |
| Working temperature | From 0 to 55 °C (recommended from 20 to 25 °C) |
| Humidity | < 95% without condensation |
| Maximum altitude | 3000 m |
| IP protection | IP20 |
| Certifications | CE (Standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classification IEC EN 62040-3) |
Jamstvo: 24 mjeseca